Resistive 400v 1500kw Load Bank 3 Phase AC Variable For Generator
Testing
Product Description
According to the special requirements of users on site, in the agreement the technical standards Intelligent Load Bank (hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.
Technical Parameters
Rating Voltage/Frequency | 400VAC 50Hz/60Hz,3phase 4 wire |
Max Load Power | Resistive Load: 1500kW |
Load Step | Resistive Load:16 steps |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | External 415VAC, 3phase 4wire 50Hz |
Wire Connection | Load Power Supply Input——Copper bar (star connection) |
Communication Interface | RS232 and RS485 |
Insulation Class | F |
Duty Cycle | Continuous |
Cooling | Forced air cooling, horizontal air inlet and air outlet |
Transportation | Hoisting, there are lifting lug in top of case and wheel castors on the bottom |
Chassis color | Gray(RAL7035) |
Size | Approximately 1900mm*2900mm*2100mm |
Weight | Approximately 2000kg |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500meters |
Atmospheric Pressure | 86~106kPa |
Product Advantage
1.High Efficiency Data Management: display real-time testing data, generate form, curve graph or report automatically, also can put data into storage. According to generator set No. set up testing file, support to query at any time, and improve data management efficiency.
2.Comprehensive Protection Function: multiple protection, like over temperature, smoke. When in danger, automatically terminate the test and give alarm to protect safety of personnel and equipment
Application
1.Manufacturers of standby power generators commonly use load banks to test and tune newly assembled units
2.generator has been set up in a test cell within the factory, a test engineer uses the load bank to apply a discrete, selectable electrical load to the generator and measure the response stability and endurance.
3.During this process, the test engineer calibrates and adjusts the generator performance to ensure it meets the intended product specifications and tolerances.
Hebei Kaixiang Electrical Technology Co., Ltd
Kaixiang intelligent power detection technology is the Chinese industry leader dedicated to providing load testing and maintenance of all types of power, to avoid accidents and economic losses due to power failure. As a national high-tech enterprises, science and technology to create the industry's first Kaixiang municipal enterprise technology center, with the establishment of China's oldest and largest intelligent power detection equipment R & D center and production base, creating the first brand of Chinese power detection "KAIXIANG Load. "
Kaixiang Technology was established in 1994, long-term focus on smart power detection technology development and application in shipbuilding, petroleum, offshore platforms, data centers, communications, power, military, aviation, research institutes and other areas, and in strict accordance with the ISO9001 international quality standard management system for the design, manufacture and service. The company's core technologies are independent research, has seven patents, 10 software copyrights, two corporate standards.Among them, Kaixiang "smart power marine generators AC load," Science and Technology Department of Hebei Province has been named the international advanced level scientific and technological achievements, the enterprise standard "dry AC load" to upgrade the industry standard by the Ministry of publicity.
Kaixiang Technology specializes in generators Intelligent Test System, HV / MV dry load, intermediate load military, RLC load, RCD nonlinear loads, renewable energy detection, smart grid - the development of micro-Grid testing and manufacturing equipment . Products have been widely used in the Jiangnan Shipyard, Huangpu Shipyard, Hudong Shipyard, CNOOC, Shengli Oilfield, CICC, Taikang Life, China Mobile, CNR, Beijing Electric Power, Beijing Institute of Technology, and other famous enterprises, institutions, but also exports to the United Kingdom, Japan, Korea, Australia, Singapore, Thailand and other overseas markets. Currently, there are over 20,000 units KaiXiang load in a well-functioning home and abroad.
KaiXiang load can be applied in shipbuilding, petroleum, offshore platforms, data centers, communications networks, financial, military, weapons, mobile power station, power plant security, mass transit, aviation, aerospace, renewable energy, smart grid - micro-grid, the instrument switches , research and teaching as well as electric vehicle charging management and other fields. Can provide users with the design, manufacture, installation, commissioning, training, maintenance of full service, as well as OEM, leasing and on-site testing services.
Kaixiang Technology at Keppel Shipyard in 2006 developed a sense of one-2926kVA resistance load is the first high-power marine dry AC load;
2009 was developed by the Huangpu Shipyard AC690V-14700K generators Intelligent Test System was the country's largest marine generator set capacity testing equipment;
2009 Zhejiang company developed high-power high-voltage AC load AC10.5kV-1760kW is China's first direct test of high-power high-voltage generators dry load;
Jiangnan Shipyard in 2010 developed AC390-12088K generators Intelligent Test System is a dry load on marine naval initial application.
Kaixiang technology to "quality-oriented, customer first" purpose, "professionalism, objectivity, innovation, efficiency" as a concept. Through our efforts, aimed at creating more value for users. We sincerely hope to cooperate with all walks of life friends, co-guardian of electrical safety, to make life better!